Intelligent
Admittance Level Limit Switch (MP-SLA...Series) |
|
|
|

Intelligent and Self
Checking
A microprocessor checks the complete
system and itself before validating the signal.
A flashing green LED serves as a heartbeat to
indicate a healthy system In the event of
occurrence of a system fault such as incorrect
wiring, open or short sensor connection, failure
of probe insulation, improper grounding or
electronic insert failure, the heartbeat stops,
fault LED glows, display indicates "E---" and
the relay contacts revert to their fail-safe
condition.
Highly Reliable
Two-wire Pulse Frequency Modulation (PFM)
is used for interference-free signal
transmission between probe and evaluation unit.
Complete system is checked before each
measurement. Auto compensation for temperature
drift in the vicinity of pre-amplifier.
High Degree of
Programmability
Features such as operating mode
(independent/pump control), delayed switching in
seconds for probe covered or uncovered
condition, fail-safe high or low, switching
sensitivity and set point calibration are
programmable via key pad. The programmed
parameters are stored in a non-volatile memory
indefinitely requiring no battery backup.
Ignores Build-Up
Special three-element probe and immunocoat
circuitry enables the system to ignore coating
on the probe, build-up from wall and suspended
dust particles, but reacts only to a true level.
Easy Calibration and
User-Friendly
All parameters are programmed via four keys and
an interactive menu-driven display leaving no
chance for incorrect entry. If recalibration is
required, the old data is displayed in the
program mode, which can be edited as desired.

Automatic Switch Point Optimisation |
|
Application |
|
Level control of solids, liquids
and slurries of
conductive/Non-conductive,
sticky/non-sticky material
requiring extreme safety and
high degree of reliability in
industries such as cement, food,
chemical and petrochemical,
effluent treatment, cosmetics,
power, plastic, material
handling, fly ash etc. |
|
Technical Data |
|
Evaluation Unit |
|
Housing |
Cast aluminium,
Weather-proof, Stoving
enamel painted, suitable
for back panel / wall
mounting. |
|
Cable Entry |
3 Nos. of ½” BSP /NPT
/NG20 |
|
Ambient Temperature: |
20º C to + 60º C. |
|
Mains |
110/230 V AC (-10 to
+10%) 50 Hz (as
specified in order). |
|
Power Consumption |
5 VA approx. |
|
Indication
(Switching) |
Red LED for each level
alarm, red LED for fault
alarm, flashing green
LED as heart-beat for
healthy condition. |
|
Indication
(calibration) |
LCD, one digit for mode
field and two digits for
data field. |
|
Response Time |
0.2 Second. Typical. |
|
Swtiching Delay |
Programmable upto 99
Second. For probe
covered/ uncovered
condition for each set
point. |
|
Connection to |
2-core ordinary cable, |
|
Electronic Insert |
having max. resistance
of 25 W per core. |
|
Initial capacitance |
20 to 1200 pF. |
|
Switching Hysterisis |
Approx. 0.5 pF at
initial |
|
(single point
operation) |
Capacitance of 30 pF. |
|
Switching Hysterisis |
Programmable over |
|
(Two point pump
control) |
entire setting range. |
|
Build-up Compensation |
Approx.
0 - 99 steps |
|
Relay Output |
One set of potential
free change over
contacts per channel
rated at 6A 230 V AC,
50Hz for non- inductive
load. |
|
Fail-Safe Mode |
: High or Low field
programmable for both
channels. |
|
Weight |
: 2.5 Kgs approx. |
|
Overall dimensions |
: 180 x 180 x 85 cm |
 |
|
Electronic Insert |
|
Housing
|
Plastic
with
electronics
potted
in epoxy
resin. |
|
Measuring
Frequency |
20º C to
80º C.
12 V at
17 mA
max.
derived
from
evaluation
unit
only. |
|
|
|
Probes |
|
Housing |
: Cast
Aluminium,
SS, FRP-coated,
HDPE. |
|
Mounting |
:
Flanged
or
Screwed
as per
requirement. |
|
Electrode
Element |
:
Special
3-element
Probe
Sense,
Shield
and
Ground. |
|
Length |
: 150mm
to 3000
mm in
Rod,
Greater
than
3000 mm
in Rope. |
|
Insulation |
: Part
or full
PVC, PTFE,
Ceramic
(Part
only)
depending
on
service
temperature
of 80º
C, 200º
C or 400º C
respectively. |
Reference
probe is
required, when
the tank is
non-metallic.
Grounding tube
is required,
when the liquid
is turbulent or
tank shape is
curved. |
|
|
|
|
|
|
|
|